Safety switch 690V 125A 3-pol+NO-NC aux.contact 2*M63/M25 IP66 Ex

IXGHG2650010R0002

ATEX and IECEx certified safety switch used to prevent unintended or unauthorized start of electrical equipment. The handle can be padlocked with your own padlock in off position. Meets EN60204-1 as emergency stop and IEC62262-1 Class 1 for maintenance. Enclosure made of impact resistant polyester.

Pack size: 1/package
In stock (0 pcs)
Estimated delivery time, if not in stock: 21 days

Rated voltage, Un
690V
Rated current, In
125A
No. of poles, auxiliary contacts
3, NO-NC auxiliary contact
Rated making/braking capacity, AC3, IEC60947-3, Ie
Ue 230-500V: Ie 125A, Ue 690V: Ie 110A
Max back-up fuse
230-500V: 200A gG, 690V 160A gG
Operator handle
Red-yellow operator, padlocable in off position for up to 3 padlocks
Enclosure
Glass-fibre reinforced polyester
Marking acc.to 214/34/EU
II 2 G Ex db eb ia IIC/IIB/IIC+H2 T6/T5 Gb, II 2 D Ex tb IIIC T80°C Db
EC type examination certificate
BVS 22 ATEX E 018 X
Marking acc.to IECEx
Exdb eb ia IIC/IIB/IIB+H2 T6/T5 Gb, Ex tb IIIC T80°C Db
IECEx certificate
IECEx BVS 22.0019X
Max permissible ambinet temperature
-55 - +55°C
Cable entry
2xM63, M25 cable gland
Terminals
50mm², auxiliary contact 4mm²
Weight,each
16kg
Manufacturer's part number
GHG2650010R0002


Safety switches, ATEX

Safety switches for installation in hazardous locations.

Safety switches 10-125A with ATEX and IECEx certification. The handle can be padlocked with your own padlock in off position used to prevent unintended or unauthorized start of electrical equipment. The switches have full AC-3 rating according to IEC60947-4-1. Designed for use in harsh environments, ingress protection IP66, and comply with Class 1 according to IEC62262-1. The switches are available as 3-pole, 4-pole or 6 pole.