Distribution block 570A 2*12-150mm²/12*2,5-25mm²

CBPDBFS377

Distribution block with UL and CSA approval. Meets the minimum spacing requirements, air and creepage, for both Branch Circuits and Feeder Circuits according to UL508A.

Pack size: 1/package
In stock (0 pcs)
Estimated delivery time, if not in stock: 28 days

Rated voltage, Un
IEC: 690V, UL:600V
Rated current, In
570A
No.of poles
1, can be multi-pole ganged
No. of openings, line side
2
Wire range, line side
150-12mm², kcmil/AWG 300-4
No. of openings, load side
12
Wire range, load side
25-2,5mm², AWG 4-14
Installation
On 35mm DIN rail
Ingress protection, IEC 60529
IP20, see catalogue for specific conditions
UL/CSA approval
UL Listed file E256146, CSA certified file 47235
Weight, each
0,34kg
Manufacturer's part number
PDBFS377


Power distribution blocks

A cost-effective alternative to busbar systems and minimizes the need to splice between various components. The power distribution blocks meet all major international standards and are CE, UL and CSA approved.

Power distribution blocks in UL 508A panels

Assembly short-circuit current rating (SCCR) is required for industrial control panels. Power distribution blocks may be one of the weakest links, an unmarked power distribution block is assigned a short-circuit current rating at 10kA. Eaton Bussmann Series power distribution blocks are UL listed according to UL1953 and meet the UL508A minimum spacing requirements, air and surface, both for Branch Circuits and Feeder Circuits. The power distribution blocks are UL listed for higher SCCR, up to 200 kA, in combination with Eaton Bussmann Series fuses and Eaton Series G MCCBs.