Surge arrestor T2 HP 1000VDC PV protection

CBSPPVT2H-10-2-PE

Protect the PV panels and the inverter against lighting and power surges. Tor reduce the risk for damages, surge protection should also be installed on the DC side.

Pack size: 1/package
In stock (0 pcs)
Estimated delivery time, if not in stock: 14 days

Classification test EN50539-11
PV T2
Technology
Metal oxide varistor
Rated voltage Un
1000VDC
Max continuous operating voltage Ucpv
1170VDC
Open circuit voltage Uoc stc
<970VDC
Short circuit current Iscpv
1000A
Rated load current Il
80A
Impulse discharge current 10/350µs Iimp
-
Impulse discharge current 80/20µs In
15kA
Response time
<25ns
Visual indication
Grey OK, red replace module
Remote indication
-
Terminal
1,5-25mm²
Ingress protection IEC60529
IP20
Weight, each
0,35kg
Manufacturer's part number
SPPVT2H-10-2-PE


Surge protection devices

Protect the PV installation on the DC side with the correct surge protection device.

A surge protection device is a sensible investment that all PV installations should be equipped with. In most cases, surge protection is recommended for PV installations on both the AC and DC side. Without surge protection on the DC side, solar panels and inverters do not have adequate protection against lightning and surges.

Our product range consists of Type 1/2 combination lightning/surge arrester and Type 2 Surge arrester for installations up to 1000VDC. If the building is equipped with an external lightning rod a type 1/2 combination lightning/surge arrester is required. For buildings without external lightning protection, Type 2 surge arrester can be used.

 

Eaton Surge protection device